Current Transformers (CTs) are used to convert high-level currents to a smaller more reasonable level for use as inputs to protection relays and metering equipment. Within electrical systems, current transformers are essential to ensure the correct functioning and control of equipment and for providing operational data and information.
This introductory note looks at the construction of
current transformers and their specification.
There are two broad categories of current transformer:
Measuring CTs – provide signals to meters and
instruments.
Protection CTs – provide signals to protective relays
to enable correct operation under steady state and transient conditions.
Current transformers work on a similar principal to normal voltage transformers. Two (or more) winding are wound round a magnetic core. Current flowing in one winding [the primary] creates a magnetic field which drives current in the other winding [the secondary]. The ratio of the primary turns to the secondary turns provides the current scaling.
Example: a 600:5 ratio CT, for every turn on the
primary would have 120 turns on the secondary. A primary current of 600 A
would cause 5 A to flow in the secondary.
The physical construction of a current transformer can
be as simple as one primary winding and one secondary winding on a core.
Quite often the construction is more complex with several secondary windings
providing different protection and instrumentation needs.
Specification of current transformers typically
considers the following:
turns ratio – of the primary to secondary current
burden – the normal load in VA that the CT can supply
accuracy factors – the accuracy limits
of (both steady state and transient)
physical configuration – the number of primary or
secondary windings, size, shape, etc.
Safety Note:If a CT secondary is not connected
to any load, then it should be short circuited. If the secondary of the
CT was left open during operation, the potential of
dangerous voltages would be induced at the secondary terminals.
Current Transformer Accuracy
Accuracy of
a current transformer is measured by the composite error. This is defined
as the difference between the ideal secondary RMS current and that of the
actual secondary current. It considers current errors, phase error and
harmonic errors.
Current transformer
intended for protection applications need to cover a wide range of
current. Then current value up to which they will maintain accuracy is
the ‘accuracy limit current’. The ratio of the accuracy limit
current to the rated current is the ‘accuracy limit factor’.
Generally, current
transformers are used to measure high currents; higher than 5A on the primary. The
most important parameter in defining a current transformer is the Ratio between
the primary and secondary.
There are two mayor groups of Current Transformers:
Protection current transformers.
Measurement current transformers.
They both have a primary current, a secondary current
and a ratio and from these 3 parameters you can define important property’s
related to accuracy for each class.
But the components of the two classes are different.
For example, in a measuring class current transformer, the core material must
have a high permeability so that the magnetizing current is low.
Measuring CT Accuracy Class
Measurement CT’s are
often being used for billing of electrical power consumption and their accuracy
is important because money is involved.
The accuracy of a
measurement CT is given by it’s accuracy class that corresponds to the error%
at rated current and at 1.2 times rated current.. The standard accuracy classes
according IEC are class 0.2, 0.5, 1, 3 and 5. For classes 3 and 5, no angle
error is specified. The classes 0.2S and 0.5S have their accuracy shifted toward
the lower currents. This means that they have 5 measuring points instead of 4
(or 2 for class 3 & 5).
Protection CT Accuracy Class
Protection Current Transformers are designed
to measure the actual currents in power systems and to produce proportional
currents in their secondary windings which are isolated from the main power
circuit. These replica currents are used as inputs to protective relays
which will automatically isolate part of a circuit in the event of an abnormal
or fault condition therein, yet permit other parts of the powersystem to
continue to operate.
Satisfactory
operation of protective relays can depend on accurate representation of
currents ranging from small leakage currents to very high overcurrent’s,
requiring the protective current transformer to be linear, and therefore below
magnetic saturation at values up to perhaps 30 times full load current .
This wide operating range means that protective
current transformers require to be constructed with larger cross-sections
resulting in heavier cores than equivalent current transformers used for
measuring duties.
This is a very basic discussion of the operation,
types, and construction of current transformers. This series on current
transformers will continue with more in-depth discussions on the accuracy and
standards assigned to current transformer.